Customized MMC-16 Trunk Cable, 16-384 Fibers, OS2

Customized MMC-16 Trunk Cable, 16-384 Fibers, OS2

The customized MMC-16 trunk is an OS2 backbone assembly built around MMC connectors based on sixteen-fiber sub-units. Fiber capacity can scale from 16 to 384 fibers, with cable outside diameter from 4.0 to 17.5mm depending on the selected construction. G.657.A1 glass, APC polish and an OFNP jacket provide the foundation for project-specific single-mode distribution.

Product Highlights

  • MMC to MMC, 16-384 Fibers
  • OS2 9/125µm, G.657.A1
  • MMC insertion loss ≤0.35dB, return loss ≥60dB
  • Trunk/ Extender Polarity wiring scheme
  • 4.0-17.5mm Plenum (OFNP) cable
  • Length and fiber count manufactured to the project requirement

Specifications

Part NumberXXMMCSMF
ManufacturerHT
Connector AUS Conec MMC
Connector BUS Conec MMC
Polish TypeAPC to APC
Glass FiberG.657.A1
Fiber ModeOS2 9/125µm
Wavelength1310/1550nm
Fiber Count16-384 Fibers
PolarityTrunk/ Extender Polarity
Cable Outside Diameter (OD)4.0-17.5mm
Cable JacketPlenum (OFNP)
Min. Bend Radius (Optical Fiber)10mm
Min. Bend Radius (Fiber Cable)20/10D (Dynamic/Static)
Tensile Strength (Long Term)200-400N
Tensile Strength (Short Term)660-1320N
Insertion Loss≤0.35dB
Return Loss≥60dB
Attenuation at 1310nm≤0.35dB/km
Attenuation at 1550nm≤0.21dB/km
Operating Temperature-10 to 60°C (14 to 140°F)
Storage Temperature-10 to 70°C (14 to 158°F)

Engineering the fiber count and cable structure

A trunk is not simply a longer jumper. As fiber count increases, sub-unit arrangement, cable diameter, pulling strength and breakout protection become part of the design. This MMC-16 family supports trunk or extender polarity and 200-400N long-term tensile ratings, with 660-1320N short-term ratings across the construction range. The exact values applicable to an order should be confirmed on its production drawing.

Backbone routes and panel coordination

Typical uses include links between optical distribution frames, equipment rows and high-density MMC panels. Pre-termination allows many fibers to be installed in one pull and tested before arrival. The panel schedule should identify every sub-unit, connector gender and polarity transition so the trunk lands correctly. High fiber counts also require adequate rear cable management and static bend space.

Specifying a made-to-project trunk

There is no assumed stock length for this customized product. Specify the route length in meters or feet, total fiber count, MMC connector gender, polarity, breakout lengths, jacket requirements and labeling. Pulling eyes or other installation protection can be discussed where the pathway requires them. Length, diameter and tensile construction are confirmed together rather than selected independently.

Ordering and Factory Support

Use XXMMCSMF as the MMC-16 trunk family reference and attach a fiber schedule or drawing. A useful enquiry includes length, fiber count, sub-unit mapping, connector gender, polarity and installation conditions, allowing the factory to quote the correct engineered assembly.

 

Get a quick quote

Please write to sales@huihongfiber.com, we will reply as soon as possible.


Huihong Technologies

Add:6F,1st Bldg,ZYT industrial park, Shiyan area,Shenzhen,China
Email:info@huihongfiber.com
Tel: 86.755.61230063
Specialized fiber optic products manufacturer.

News and Exhibitions

Company news and exhibitions schedules for this year and next year. click here for details .
Thank you for visiting with Huihong Technologies.

Fiber Optic Applications

  • Fiber Optic Interconnect
  • Data centers
  • Military Fiber Optics
  • Medical Fiber Optics
  • Broadcast Fiber Optics

Customer Support

customer support
Thank you for the inquiry, please email sales@huihongfiber.com, we will reply to you asap.